Research on fault location based on PMU for multi-source distribution network

Zhang Mengsheng, Wang Yi, Zhiguo Zhou, Zufu Li

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

5 Citations (Scopus)

Abstract

Accurate fault location is beneficial for the stability of power distribution network. With the access of distributed energy resource, such as distributed generations, electric vehicles, controllable load and so on, traditional fault and protection device has been unable to completely adopt to the new situation of distribution network protection, which requires new technologies and devices. In this paper, a new method based on phasor measurement unit, termed PMU or synchrophasor, is proposed to locate the fault in the multi-source distribution network. The location method uses the voltage and current information of PMU on one terminal to iterating every line segment, the candidate faults and its fault distance are calculated. By means of voltage phase relationship between fault voltage and measured voltage of PMUs on two terminals to get the actual fault location and eliminate the pseudo fault locations, with the characteristic of high-precision and clock synchronization in PMU. Finally, the simulation results show that the location method has high position accuracy in the multi-source distribution network by the algorithm simulation analysis based on Matlab/Simulink platform. The method can satisfy different types of fault with simply installing PMUs only on the two terminals of the circuit. And still has high location accuracy with the influence of high DG penetration and high resistance faults.

Original languageEnglish
Title of host publicationIEEE PES APPEEC 2016 - 2016 IEEE PES Asia Pacific Power and Energy Engineering Conference
PublisherIEEE Computer Society
Pages1877-1882
Number of pages6
ISBN (Electronic)9781509054183
DOIs
Publication statusPublished - 9 Dec 2016
Event2016 IEEE PES Asia Pacific Power and Energy Engineering Conference, APPEEC 2016 - Xi'an, China
Duration: 25 Oct 201628 Oct 2016

Publication series

NameAsia-Pacific Power and Energy Engineering Conference, APPEEC
Volume2016-December
ISSN (Print)2157-4839
ISSN (Electronic)2157-4847

Conference

Conference2016 IEEE PES Asia Pacific Power and Energy Engineering Conference, APPEEC 2016
Country/TerritoryChina
CityXi'an
Period25/10/1628/10/16

Keywords

  • PMU
  • distributed generation
  • fault location
  • high impedance fault
  • multi-source distribution network

Fingerprint