N2 - A temperature sensitive self-starting fire extinguishing pipe system with no power supply was designed for closed space fire accident of electric vehicle battery box. The fire source was simulated using n-heptane. The test was carried out in a test chamber using perfluorohexanone and hexafluoropropane as the extinguishing medium. The fire extinguishing process, pressure change in the pipe, use rate of fire extinguishing agent and fire extinguishing time were analyzed under the pressure of 0, 0. 88 and 1. 81 MPa. The results show that the fire extinguishing process of perfluorohexanone and hexafluoropropane fire pipe systems is similar, which can be divided into three stages: preheating-pipe rupture jet-flame extinguishing and continued jetting, that the actual use rate of extinguishing agent for hexafluoropropane fire extinguishing pipe system is 100%, that the actual use rate of perfluorohexanone fire extinguishing pipe system is between 50% and 95%, and the increase of pressure greatly increases the actual use rate of perfluorohexanone, that the hexafluoropropane fire extinguishing pipe system can extinguish the fire within 20 s, and that the fire extinguishing time of the perfluorohexanone fire extinguishing pipe system is longer than that of hexafluoropropane fire extinguishing pipe system.
AB - A temperature sensitive self-starting fire extinguishing pipe system with no power supply was designed for closed space fire accident of electric vehicle battery box. The fire source was simulated using n-heptane. The test was carried out in a test chamber using perfluorohexanone and hexafluoropropane as the extinguishing medium. The fire extinguishing process, pressure change in the pipe, use rate of fire extinguishing agent and fire extinguishing time were analyzed under the pressure of 0, 0. 88 and 1. 81 MPa. The results show that the fire extinguishing process of perfluorohexanone and hexafluoropropane fire pipe systems is similar, which can be divided into three stages: preheating-pipe rupture jet-flame extinguishing and continued jetting, that the actual use rate of extinguishing agent for hexafluoropropane fire extinguishing pipe system is 100%, that the actual use rate of perfluorohexanone fire extinguishing pipe system is between 50% and 95%, and the increase of pressure greatly increases the actual use rate of perfluorohexanone, that the hexafluoropropane fire extinguishing pipe system can extinguish the fire within 20 s, and that the fire extinguishing time of the perfluorohexanone fire extinguishing pipe system is longer than that of hexafluoropropane fire extinguishing pipe system.
KW - closed space
KW - electric vehicle fire
KW - extinguishing agent usage rate
KW - fire extinguishing time
KW - pressure change
KW - temperature-sensing self-starting fire extinguishing pipe system
UR - http://www.scopus.com/inward/record.url?scp=85159201799&partnerID=8YFLogxK
U2 - 10.16265/j.cnki.issn1003-3033.2019.11.010
DO - 10.16265/j.cnki.issn1003-3033.2019.11.010
M3 - 文章
AN - SCOPUS:85159201799
SN - 1003-3033
VL - 29
SP - 58
EP - 63
JO - China Safety Science Journal
JF - China Safety Science Journal
IS - 11
ER -