Combined application of SEDC and GTSDC for SSR mitigation and its field tests

Xiaorong Xie, Liang Wang, Yingduo Han

科研成果: 期刊稿件文章同行评审

31 引用 (Scopus)

摘要

The subsynchronous resonance (SSR) problem may become more serious with the continuous evolvement of a series-compensated power system. Consequently, the existing SSR mitigation scheme might no longer keep the system stable. This issue has been encountered by Shangdu Power Plant, where the deployed supplementary excitation damping controllers (SEDCs) that well stabilized the system before cannot maintain torsional stability after the recent change occurred in the power system. Therefore, a combined mitigation scheme of SEDC and generator terminal subsynchronous damping controller (GTSDC) is proposed in this paper to regain system stability. SEDC provides electrical damping by modulating the excitation voltage at the rotor side. Meanwhile, GTSDC can damp SSR via injecting super-synchronous and subsynchronous currents into the generator stator. Field tests have proven the effectiveness of this combined scheme in addressing the deteriorated SSR issue. Eigenvalue analysis indicates that the combined scheme can provide enough positive damping for the system under any operating condition. Thanks to the low investment of SEDC and the flexibility of GTSDC, this combined scheme provides an economical and scalable solution for SSR mitigation, especially when the target system changes constantly.

源语言英语
文章编号7031968
页(从-至)769-776
页数8
期刊IEEE Transactions on Power Systems
31
1
DOI
出版状态已出版 - 1月 2016

指纹

探究 'Combined application of SEDC and GTSDC for SSR mitigation and its field tests' 的科研主题。它们共同构成独一无二的指纹。

引用此