A dynamic strategy to improve the ride-through capability of a fixed speed induction generator

Lucheng Hong*, Qirong Jiang, Liang Wang

*此作品的通讯作者

科研成果: 期刊稿件文章同行评审

3 引用 (Scopus)

摘要

Based on the analysis of the short current of the fixed speed induction generator (FSIG) under symmetrical system faults, a strategy using the dynamic voltage restorer (DVR) is proposed to improve the low-voltage ride through (LVRT) capability of FSIGs. During the system fault, LVRT-DVR is connected in series between the grid and the generator by switching-off the by-pass bidirectional thyristors and provides a compensating voltage to isolate FSIG from the system fault. To increase the switch-in speed of LVRT-DVR, an antivoltage technique is used to shut the thyristors off immediately. After the fault is cleared, the phase-shifting control is applied to avoid phase jumps of the FSIG terminal voltage. The PSCAD/EMTDC simulation and field tests have been carried out to prove the effectiveness of the proposed LVRT strategy, and related conclusions and comments are summarized.

源语言英语
文章编号e2538
期刊International Transactions on Electrical Energy Systems
28
5
DOI
出版状态已出版 - 5月 2018