Wide-area robust H control with pole placement for damping inter-area oscillations

He Chen*, Hong Bai, Ming Liu, Zhizhong Guo

*此作品的通讯作者

科研成果: 书/报告/会议事项章节会议稿件同行评审

19 引用 (Scopus)

摘要

A wide-area robust control method for damping inter-area oscillations of power system is suggested in this paper. Both local and PMU-provided remote signals are utilized as feedback inputs to the controller. Participation vector is used to select remote signal and position controller. The damping controller design is formulated as an output disturbance rejection problem based on the mixed-sensitivity formulation and with pole placement constraints. This multi-objective synthesis can be transformed into a standard linear matrix inequality (LMI) problem which can be tractable numerically. A 4- generator power system is used to illustrate the whole design procedure and demonstrate the effectiveness of the designed controller and robustness with respect to variations of the system operating conditions. The results are also compared with the conventional PSS damping control.

源语言英语
主期刊名2006 IEEE PES Power Systems Conference and Exposition, PSCE 2006 - Proceedings
2101-2108
页数8
DOI
出版状态已出版 - 2006
已对外发布
活动2006 IEEE PES Power Systems Conference and Exposition, PSCE 2006 - Atlanta, GA, 美国
期限: 29 10月 20061 11月 2006

出版系列

姓名2006 IEEE PES Power Systems Conference and Exposition, PSCE 2006 - Proceedings

会议

会议2006 IEEE PES Power Systems Conference and Exposition, PSCE 2006
国家/地区美国
Atlanta, GA
时期29/10/061/11/06

指纹

探究 'Wide-area robust H control with pole placement for damping inter-area oscillations' 的科研主题。它们共同构成独一无二的指纹。

引用此