TY - JOUR
T1 - Termination Control Temperature Study for an Air Source Heat Pump Unit during Its Reverse Cycle Defrosting
AU - Song, Mengjie
AU - Wang, Xuanjie
AU - Liao, Liyuan
AU - Deng, Shiming
N1 - Publisher Copyright:
© 2017 The Authors. Published by Elsevier Ltd.
PY - 2017
Y1 - 2017
N2 - For an air source heat pump (ASHP) unit with a vertically installed multi-circuit outdoor coil, a reverse cycle defrosting (RCD) operation is always terminated when the tube surface temperature at the exit of the lowest circuit reaches a pre-set value. It is obviously that when the pre-set temperature is higher, the defrosting duration would be prolonged. Not only more energy would be consumed on heating cold ambient air, but also the occupants' thermal comfort adversely affected. However, if the pre-set temperature is lower, more residual water would be left on the downside surface of fin in an outdoor coil, which degrades the system performance during the next frosting/defrosting cycle. In order to find a suitable DTT or its range, in this paper, an experimental investigation on RCD operation for an ASHP unit with a multi-circuit outdoor coil was conducted and reported. As concluded, DTT is suitable at the range of 20-25 °C, around 22 °C.
AB - For an air source heat pump (ASHP) unit with a vertically installed multi-circuit outdoor coil, a reverse cycle defrosting (RCD) operation is always terminated when the tube surface temperature at the exit of the lowest circuit reaches a pre-set value. It is obviously that when the pre-set temperature is higher, the defrosting duration would be prolonged. Not only more energy would be consumed on heating cold ambient air, but also the occupants' thermal comfort adversely affected. However, if the pre-set temperature is lower, more residual water would be left on the downside surface of fin in an outdoor coil, which degrades the system performance during the next frosting/defrosting cycle. In order to find a suitable DTT or its range, in this paper, an experimental investigation on RCD operation for an ASHP unit with a multi-circuit outdoor coil was conducted and reported. As concluded, DTT is suitable at the range of 20-25 °C, around 22 °C.
KW - Air source heat pump
KW - Defrosting termination temperature
KW - Experimental study
KW - Multi-circuit outdoor coil
KW - Reverse cycle defrosting
UR - http://www.scopus.com/inward/record.url?scp=85020723325&partnerID=8YFLogxK
U2 - 10.1016/j.egypro.2017.03.323
DO - 10.1016/j.egypro.2017.03.323
M3 - Conference article
AN - SCOPUS:85020723325
SN - 1876-6102
VL - 105
SP - 335
EP - 342
JO - Energy Procedia
JF - Energy Procedia
T2 - 8th International Conference on Applied Energy, ICAE 2016
Y2 - 8 October 2016 through 11 October 2016
ER -