Simulation and analysis of the indoors thermal environment in the high elevated waiting hall of Kunming railway station

Shu Li Liu*, Jun Lu, Liu Nian Luo, Hong Zhang, Sheng He, Hai Yan Huang

*此作品的通讯作者

科研成果: 期刊稿件文章同行评审

摘要

The high-elevated waiting hall of Kunming railway station is 72.65 meters long, 39.4 meters wide and 8.85 meters high. There are large glass curtain walls all around the waiting hall and on the roof there are day lighting lines. It is likely to be overheated in summer. The software PHOENICS is used to carry out a numerical test on the waiting hall under the original design condition and the improving measures, some advices are given. Through analyzing four different schemes, a solution is gained: increase the number of vents on the roof; cancel the day lighting lines; broaden the gate on east wall. It is the best one of recommended means. The thermal environment and the wind field of the waiting hall are also simulated. Not only the ventilation but also the indoor temperature lower than 27°C is guaranteed, which meets the requirements for the people is activity in the hall.

源语言英语
页(从-至)76-79
页数4
期刊Chongqing Jianzhu Daxue Xuebao/Journal of Chongqing Jianzhu University
27
2
出版状态已出版 - 4月 2005
已对外发布

指纹

探究 'Simulation and analysis of the indoors thermal environment in the high elevated waiting hall of Kunming railway station' 的科研主题。它们共同构成独一无二的指纹。

引用此