TY - JOUR
T1 - An investigation on shell-side thermal–hydraulic performance of helically coiled tube heat exchanger for deep underground space
AU - Wang, Yijiang
AU - Wang, Yangjie
AU - Sun, Li
AU - Yang, Jinhong
AU - Zhong, Hua
N1 - Publisher Copyright:
© 2024 Elsevier Ltd
PY - 2024/7/1
Y1 - 2024/7/1
N2 - Helically coiled tube heat exchanger (HCHE) was extensively used to enhance the thermal environment of deep underground space. The inefficiency of heat transfer in the mine cooling system results in increased operational energy consumption. To enhance heat utilization, this study examines the impact of air temperature, air velocity, coil diameter, pitch, and elliptical tube aspect ratio on the shell-side thermal performance of HCHE through experimental and numerical analysis. The performance evaluation criterion (PEC) and field synergy are introduced to provide a comprehensive assessment of performance. Results suggest that the air velocity can more significantly affect the thermal performance of HCHE than air temperature. Augmenting the coil diameter from 30 − 40 mm and coil pitch from 7.5 − 9.0 mm led to an increase in the Nu number by 16.5 % and 6.7 %, as well as an increase in friction factor f by 575.2 % and 147.1 %, while a reduction in PEC by 38.4 % and 21.1 % when the air velocity is 5 m/s, respectively. For the helically coiled elliptical-tube heat exchanger (HCHE-E), the thermal performance is significantly dependent on the long axis's direction and its aspect ratio. When the air velocity is 3 m/s, the increase in aspect ratio from 1.0 to 1.8 resulted in a decrease and increase in Nu by 14.7 % and 14.6 %, an increase and decrease in PEC by 24.5 % and 28.4 %, as well as a reduction and increase in f by 31.5 % and 48.1 % for the long axle in the horizontal and vertical directions, respectively. The PEC for HCHE is not significantly dependent on the air velocity. The increase in air velocity can result in the augment in PEC of HCHE-E regardless of long axis's direction. The variation of synergy angle is consistent with the change of Nu. These findings offer valuable insights for optimizing the design parameters of HCHE in deep underground spaces.
AB - Helically coiled tube heat exchanger (HCHE) was extensively used to enhance the thermal environment of deep underground space. The inefficiency of heat transfer in the mine cooling system results in increased operational energy consumption. To enhance heat utilization, this study examines the impact of air temperature, air velocity, coil diameter, pitch, and elliptical tube aspect ratio on the shell-side thermal performance of HCHE through experimental and numerical analysis. The performance evaluation criterion (PEC) and field synergy are introduced to provide a comprehensive assessment of performance. Results suggest that the air velocity can more significantly affect the thermal performance of HCHE than air temperature. Augmenting the coil diameter from 30 − 40 mm and coil pitch from 7.5 − 9.0 mm led to an increase in the Nu number by 16.5 % and 6.7 %, as well as an increase in friction factor f by 575.2 % and 147.1 %, while a reduction in PEC by 38.4 % and 21.1 % when the air velocity is 5 m/s, respectively. For the helically coiled elliptical-tube heat exchanger (HCHE-E), the thermal performance is significantly dependent on the long axis's direction and its aspect ratio. When the air velocity is 3 m/s, the increase in aspect ratio from 1.0 to 1.8 resulted in a decrease and increase in Nu by 14.7 % and 14.6 %, an increase and decrease in PEC by 24.5 % and 28.4 %, as well as a reduction and increase in f by 31.5 % and 48.1 % for the long axle in the horizontal and vertical directions, respectively. The PEC for HCHE is not significantly dependent on the air velocity. The increase in air velocity can result in the augment in PEC of HCHE-E regardless of long axis's direction. The variation of synergy angle is consistent with the change of Nu. These findings offer valuable insights for optimizing the design parameters of HCHE in deep underground spaces.
KW - Flow resistance
KW - Heat transfer coefficient
KW - Helically coiled tube heat exchanger
KW - Performance evaluation criterion
KW - Synergy angle
UR - http://www.scopus.com/inward/record.url?scp=85190341305&partnerID=8YFLogxK
U2 - 10.1016/j.applthermaleng.2024.123157
DO - 10.1016/j.applthermaleng.2024.123157
M3 - Article
AN - SCOPUS:85190341305
SN - 1359-4311
VL - 248
JO - Applied Thermal Engineering
JF - Applied Thermal Engineering
M1 - 123157
ER -