A study on multi-nozzle arrangement for spray cooling system in natural draft dry cooling tower

Yubiao Sun*, Zhiqiang Guan, Hal Gurgenci, Xiaoxiao Li, Kamel Hooman

*此作品的通讯作者

科研成果: 期刊稿件文章同行评审

57 引用 (Scopus)

摘要

Natural draft dry cooling tower (NDDCT) technology is especially attractive to power plants built in arid regions with limited water resource. However, high ambient temperature in summer deteriorates the performance of built NDDCT. To address this problem, evaporative pre-cooling technology has been developed by using nozzles to disintegrate water into fine droplets to achieve quick evaporation. The pre-cooled air flowing through radiator, has an enhanced heat exchange with the hot working fluid in the tube side. This paper reports a spray cooling system for the experimental tower built in UQ by combining several nozzle LNN1.5 to cool the inlet air and consequently improve the cooling efficiency of the NDDCT. To minimize water usage, a careful arrangement of spray nozzles should be investigated to achieve the maximum cooling outcome. With five nozzles installment, the inlet air is cooled by 6.3 °C, corresponding to 51.2% cooling efficiency. A dimensionless analysis is presented to correlate cooling efficiency with influencing factors. The advantage of this pre-cooling system lies in the efficient water usage: more than 96% of the injected water extracts substantial heat from hot air and evaporates into vapor, leading to a pre-cooled airflow.

源语言英语
页(从-至)795-814
页数20
期刊Applied Thermal Engineering
124
DOI
出版状态已出版 - 2017
已对外发布

指纹

探究 'A study on multi-nozzle arrangement for spray cooling system in natural draft dry cooling tower' 的科研主题。它们共同构成独一无二的指纹。

引用此