TY - JOUR
T1 - Experimental investigations on destroying surface tension of melted frost for defrosting performance improvement of a multi-circuit outdoor coil
AU - Song, Mengjie
AU - Mao, Ning
AU - Deng, Shiming
AU - Chen, Ying
AU - Wang, Chao
AU - Yang, Qingcheng
N1 - Publisher Copyright:
© 2016 Elsevier Ltd. All rights reserved.
PY - 2016/6/25
Y1 - 2016/6/25
N2 - When frost forms and accumulates over the outdoor coil's surface in an air source heat pump (ASHP) unit, system operating performance will be adversely affected. Currently, reverse cycle defrosting is the most widely used standard defrosting method. A previous related study suggested that, for an ASHP unit with a multi-circuit outdoor coil, water collecting trays installed between circuits could eliminate the negative effects of downwards flowing melted frost due to gravity. However, for a vertical multi-circuit outdoor coil with separations, there is also a lot of melted frost remained on the downside surface of each circuit due to surface tension. The remained water would consume energy, and thus deteriorate system defrosting performance. To quantitatively study the negative effects of surface tension, in this paper, an experimental study changing the vertical multi-circuit outdoor coil into horizontally installed in an ASHP unit was conducted. Compared with the surface tension kept, defrosting duration could be shorted from 186 s to 167 s, or 20 s less, and defrosting efficiency improved from 49.4% to 61.4%, or 12.0% more, when the remained water cleaned as the surface tension destroyed.
AB - When frost forms and accumulates over the outdoor coil's surface in an air source heat pump (ASHP) unit, system operating performance will be adversely affected. Currently, reverse cycle defrosting is the most widely used standard defrosting method. A previous related study suggested that, for an ASHP unit with a multi-circuit outdoor coil, water collecting trays installed between circuits could eliminate the negative effects of downwards flowing melted frost due to gravity. However, for a vertical multi-circuit outdoor coil with separations, there is also a lot of melted frost remained on the downside surface of each circuit due to surface tension. The remained water would consume energy, and thus deteriorate system defrosting performance. To quantitatively study the negative effects of surface tension, in this paper, an experimental study changing the vertical multi-circuit outdoor coil into horizontally installed in an ASHP unit was conducted. Compared with the surface tension kept, defrosting duration could be shorted from 186 s to 167 s, or 20 s less, and defrosting efficiency improved from 49.4% to 61.4%, or 12.0% more, when the remained water cleaned as the surface tension destroyed.
KW - Air source heat pump
KW - Experiment
KW - Remained water
KW - Reverse cycle defrosting
KW - Surface tension
UR - http://www.scopus.com/inward/record.url?scp=84966263973&partnerID=8YFLogxK
U2 - 10.1016/j.applthermaleng.2016.03.173
DO - 10.1016/j.applthermaleng.2016.03.173
M3 - Article
AN - SCOPUS:84966263973
SN - 1359-4311
VL - 103
SP - 1278
EP - 1288
JO - Applied Thermal Engineering
JF - Applied Thermal Engineering
ER -