Experimental investigations of an absorption heat pump prototype with intermediate process for residential district heating

Ding Lu, Yin Bai, Yanxing Zhao, Xueqiang Dong, Maoqiong Gong*, Ercang Luo, Gaofei Chen, Qingyu Xu, Jun Shen

*Corresponding author for this work

Research output: Contribution to journalArticlepeer-review

23 Citations (Scopus)

Abstract

Despite being efficient means of district heating, conventional single-effect absorption heat pumps suffer significant performance deterioration at low ambient temperatures. To solve this problem, an ammonia-water absorption heat pump prototype with intermediate process is designed and built. It utilizes both low-grade heat from the ambient and exhaust heat from natural gas combustion, through the evaporator and intermediate evaporator, respectively. To perform comparison study, the prototype also has the single-effect mode. Experimental results indicate that when the evaporation temperature is 0 °C, the prototype with intermediate process can provide 30 kW heating capacity to heat the water in sequence through the rectifier, condenser and absorber, from 34.24 to 55.09 °C, and the coefficient of performance and primary energy efficiency are 1.66 and 1.28, respectively. When evaporation temperatures reduce to −5, −10 and −15 °C, the coefficient of performances are 1.51, 1.40 and 1.28, respectively, reaching 77%–90% of the simulation values under corresponding working conditions. Compared to the conventional single-effect system, the prototype with intermediate process performs better at lower evaporation temperature, with the coefficient of performance improved by 11%. By replacing the original heat exchangers, the proposed system can be easily applied to the existing heat networks based on gas-fired boilers to improve energy efficiency, and the favorable experimental performance proves that it is a more efficient way of residential district heating, especially in cold regions.

Original languageEnglish
Article number112323
JournalEnergy Conversion and Management
Volume204
DOIs
Publication statusPublished - 15 Jan 2020
Externally publishedYes

Keywords

  • Absorption heat pump
  • District heating
  • Experimental study
  • Intermediate process
  • Natural gas
  • Waste heat recovery

Fingerprint

Dive into the research topics of 'Experimental investigations of an absorption heat pump prototype with intermediate process for residential district heating'. Together they form a unique fingerprint.

Cite this