摘要
A heating system achieved by combining thermochemical energy storage and absorption heat pump is proposed and verified. Based on the experimental data, a mathematical model of the zeolite/water reactor is established and verified. By setting up a micro-compressor between the evaporator and absorber, the AHP is driven by low temperature source. Based on typical days in winter, the stable operation of the system is explored, and the influence of main parameters on the charging/discharging and heating processes are analyzed. The results show that the charging and heating efficiency reached 55.11% and 73.52% during the daytime. The discharging efficiency at night reaches 88.27%. The AHP can be driven by a heat source at a minimum of 75 °C, and hot water at 48.3 °C is provided. Parameters influence analysis shows that temperature is an important factor affecting the charging process, and the initial air temperature is recommended to increase. Humidity is the biggest influencing factor in the discharging process and easily changed and controlled. By replacing electric heating, the system can allow the investment to be recovered within 6.23 years.
| 源语言 | 英语 |
|---|---|
| 期刊论文编号 | 123820 |
| 期刊 | Applied Energy |
| 卷 | 372 |
| DOI | |
| 出版状态 | 已出版 - 15 10月 2024 |
联合国可持续发展目标
此成果有助于实现下列可持续发展目标:
-
可持续发展目标 7 经济适用的清洁能源
学术指纹
探究 'Performance optimization and evaluation of integrating thermochemical energy storage with low-temperature driven absorption heat pump for building heating: 4E analyses' 的科研主题。它们共同构成独一无二的学术指纹。引用此
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver