跳到主要导航 跳到搜索 跳到主要内容

10-kV transmission line experimental platform for HEMP immunity test of electrical equipment in operation

  • Yu Hao Chen
  • , Yan Zhao Xie
  • , Dao Zhong Zhang
  • , Yi Zhou
  • , De Chang Ren
  • , Ming Yue Gou
  • , Ning Dong
  • School of Electrical Engineering

科研成果: 期刊稿件 › 文章 › 同行评审

摘要

To investigate the high-altitude electromagnetic pulse (HEMP) immunity of electrical equipment in operation, a 10-kV transmission line (TL) experimental platform is built in this paper. The conducted transient electromagnetic disturbance (TED) could be injected to the electrical equipment of 10-kV TL with power on or power off. The TED is produced by the pulsed current injection (PCI) generator, whose rise time is less than 20 ns and full width at half maximum is in the range of 500 ∼ 550 ns on short-circuit state with 60 Ω resistor. On the other hand, the 10-kV TL is equivalently designed in cross section to make its characteristic impedance being 330 Ω to conform to the value of practical case. The voltages and currents applied on the tested equipment can be measured at nano-second level simultaneously, which are of great use to learn the effect mechanisms and compare the results under different working conditions. Some 10-kV pin-type porcelain insulators are tested under different conditions, which shows the capacity of the proposed platform to test immunity of 10-kV electrical equipment.

源语言英语
期刊论文编号9112239
页(从-至)1034-1040
页数7
期刊IEEE Transactions on Power Delivery
卷36
期2
DOI
出版状态已出版 - 4月 2021
已对外发布是

学术指纹

探究 '10-kV transmission line experimental platform for HEMP immunity test of electrical equipment in operation' 的科研主题。它们共同构成独一无二的学术指纹。

引用此