跳到主要导航 跳到搜索 跳到主要内容

基于提升小波和Hilbert变换的暂态电能质量检测

  • Beijing Institute of Technology

科研成果: 期刊稿件文章同行评审

摘要

In oeder to improve the location accuracy and the type identification speed of disturbance in the transient power quality detection, a lifting wavelet and Hilbert transform fusion method was proposed in this paper. Firstly, the lifting wavelet was employed to get signal approximation components A1 and detail components D1 from the disturbed signals. And then, the Hilbert transform was used to calculate the instantaneous amplitude of the two components. According to the instantaneous amplitude, the disturbance time and type were identified accurately. Simulation and experiment results show that, the disturbance time location accuracy can reach 95.7% and the type identification accuracy can reach 91.8% based on the proposed method.

投稿的翻译标题A Lifting Wavelet and Hilbert Transform Fusion Method for Transient Power Quality Detection
源语言繁体中文
页(从-至)162-168
页数7
期刊Beijing Ligong Daxue Xuebao/Transaction of Beijing Institute of Technology
39
2
DOI
出版状态已出版 - 1 2月 2019

关键词

  • Disturbance identification
  • Disturbance location
  • Hilbert transform
  • Lifting wavelet
  • Transient power quality

指纹

探究 '基于提升小波和Hilbert变换的暂态电能质量检测' 的科研主题。它们共同构成独一无二的指纹。

引用此