Fault tolerant control for steam generators in nuclear power plant

  • Zhi Hong Deng*
  • , Xiao Cheng Shi
  • , Guo Qing Xia
  • , Ming Yu Fu
  • *Corresponding author for this work

Research output: Contribution to journalArticlepeer-review

12 Citations (Scopus)

Abstract

Based on the nonlinear system with stochastic noise, a bank of extended Kalman filters is used to estimate the state of sensors. It can real-time detect and isolate the single sensor fault, and reconstruct the sensor output to keep steam generator water level stable. The simulation results show that the methodology of employing a bank of extended Kalman filters for steam generator fault tolerant control design is feasible.

Original languageEnglish
Pages (from-to)107-111+116
JournalHedongli Gongcheng/Nuclear Power Engineering
Volume31
Issue number1
Publication statusPublished - Feb 2010
Externally publishedYes

Keywords

  • Extended Kalman filter
  • Fault tolerant control
  • Nonlinear
  • Steam generator