Fault identification of high-voltage cable sheath grounding system based on ground current analysis

Bangle He, Yunjie Zhou, Hai Li, Ting Ye, Shifeng Fan, Xiaodi Wang

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

13 Citations (Scopus)

Abstract

In order to reduce the induced voltage of the metal sheath of the high-voltage cable, the metal sheath of the high-voltage cable is usually cross-connected in the transposition box of the cable cross-interconnection. In the process of reconnecting the cable line, the transposition is easy to be connected backwards, or even wrong. In addition, there will be many situations such as moisture, water intrusion, external force damage, resulting in cross-interconnection failures in the metal sheath of the high-voltage cable. Cross-connect faults need to be dealt with in time. The paper analyzes the cross-connect faults of 110kV XLPE high-voltage cables, and uses PSCAD electromagnetic transient software to model and simulate. Simulation results summarize the characteristics of grounding current changes under different sheath faults. The results can provide a theoretical basis for the fault detection of the cable cross transposition system.

Original languageEnglish
Title of host publication2020 IEEE 4th Conference on Energy Internet and Energy System Integration
Subtitle of host publicationConnecting the Grids Towards a Low-Carbon High-Efficiency Energy System, EI2 2020
PublisherInstitute of Electrical and Electronics Engineers Inc.
Pages3248-3251
Number of pages4
ISBN (Electronic)9781728196060
DOIs
Publication statusPublished - 30 Oct 2020
Externally publishedYes
Event4th IEEE Conference on Energy Internet and Energy System Integration, EI2 2020 - Wuhan, China
Duration: 30 Oct 20201 Nov 2020

Publication series

Name2020 IEEE 4th Conference on Energy Internet and Energy System Integration: Connecting the Grids Towards a Low-Carbon High-Efficiency Energy System, EI2 2020

Conference

Conference4th IEEE Conference on Energy Internet and Energy System Integration, EI2 2020
Country/TerritoryChina
CityWuhan
Period30/10/201/11/20

Keywords

  • Cross-connect
  • Ground current
  • High-voltage cable
  • PSCAD/EMTDC simulation

Fingerprint

Dive into the research topics of 'Fault identification of high-voltage cable sheath grounding system based on ground current analysis'. Together they form a unique fingerprint.

Cite this