Skip to main navigation Skip to search Skip to main content

Fast voltage detection method for grid-tied renewable energy generation systems under distorted grid voltage conditions

  • Furong Xiao
  • , Lei Dong*
  • , Li Li
  • , Xiaozhong Liao
  • *Corresponding author for this work
  • Beijing Institute of Technology
  • University of Technology Sydney

Research output: Contribution to journalArticlepeer-review

Abstract

A fast voltage detection method to assist with the low-voltage ride-through operation of grid-tied renewable energy generation systems is proposed in this study. It is designed to detect every phase voltage, so that it can be applied in both three-phase and single-phase applications. The whole voltage detection approach consists of two stages, the pre-filtering stage and the voltage detection stage. In the pre-filtering stage, a cascaded delayed signal cancellation (CDSC) module and a low-pass filter are connected in series to filter low-order harmonics and high-frequency noises. For eliminating the low-order harmonics of interest, different types of CDSC methods are studied in detail. Subsequently, a new orthogonal signal generator is built to calculate the voltage amplitude in the voltage detection stage. Finally, the proposed voltage detection method is verified by experimental results.

Original languageEnglish
Pages (from-to)1487-1493
Number of pages7
JournalIET Power Electronics
Volume10
Issue number12
DOIs
Publication statusPublished - 6 Oct 2017

UN SDGs

This output contributes to the following UN Sustainable Development Goals (SDGs)

  1. SDG 7 - Affordable and Clean Energy
    SDG 7 Affordable and Clean Energy

Fingerprint

Dive into the research topics of 'Fast voltage detection method for grid-tied renewable energy generation systems under distorted grid voltage conditions'. Together they form a unique fingerprint.

Cite this