Abstract
A fast voltage detection method to assist with the low-voltage ride-through operation of grid-tied renewable energy generation systems is proposed in this study. It is designed to detect every phase voltage, so that it can be applied in both three-phase and single-phase applications. The whole voltage detection approach consists of two stages, the pre-filtering stage and the voltage detection stage. In the pre-filtering stage, a cascaded delayed signal cancellation (CDSC) module and a low-pass filter are connected in series to filter low-order harmonics and high-frequency noises. For eliminating the low-order harmonics of interest, different types of CDSC methods are studied in detail. Subsequently, a new orthogonal signal generator is built to calculate the voltage amplitude in the voltage detection stage. Finally, the proposed voltage detection method is verified by experimental results.
| Original language | English |
|---|---|
| Pages (from-to) | 1487-1493 |
| Number of pages | 7 |
| Journal | IET Power Electronics |
| Volume | 10 |
| Issue number | 12 |
| DOIs | |
| Publication status | Published - 6 Oct 2017 |
UN SDGs
This output contributes to the following UN Sustainable Development Goals (SDGs)
-
SDG 7 Affordable and Clean Energy
Fingerprint
Dive into the research topics of 'Fast voltage detection method for grid-tied renewable energy generation systems under distorted grid voltage conditions'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver