Abstract
Due to the increased fault-level currents, superconducting fault current limiter (SFCL) is more likely to penetrate into a low voltage and medium voltage transmission network to improve their stability and lower the electric devices capacity. Therefore it is important to model a SFCL in power system to analyze its performance and study its characteristics. In this paper, a simulation model for a resistive type SFCL consisted of YBCO tapes is developed using Matlab/Simulink software. This model will take into account SFCL's internal electromagnetic behavior by coupling its internal resistance and the current density characteristics based on the E-J power law. Finally, the SFCL simulation model is applied in a transmission and a wind farm power grid, respectively. Different fault limiting scenarios are investigated and the results show that the SFCL is effective in limiting fault currents with a maximum of 50% in transmission lines, particularly for wind farm networks.
Original language | English |
---|---|
Pages (from-to) | 716-721 |
Number of pages | 6 |
Journal | Energy Procedia |
Volume | 75 |
DOIs | |
Publication status | Published - 2015 |
Externally published | Yes |
Event | 7th International Conference on Applied Energy, ICAE 2015 - Abu Dhabi, United Arab Emirates Duration: 28 Mar 2015 → 31 Mar 2015 |
Keywords
- Resistive type superconducting fault current limiter (SFCL)
- YBCO
- simulation
- transmission lines
- wind farm