TY - JOUR
T1 - Developing condensing-frosting performance maps for a variable speed air source heat pump (ASHP) for frosting suppression
AU - Liu, Shengnan
AU - Bai, Xiaoxia
AU - Zhang, Long
AU - Lin, Yao
AU - Deng, Shiming
AU - Wang, Wei
AU - Wei, Minchen
N1 - Publisher Copyright:
© 2022 Elsevier Ltd
PY - 2022/7/5
Y1 - 2022/7/5
N2 - For a space heating ASHP unit, frosting on its outdoor coil would adversely impact its normal operation, requiring frequent defrosting and resulting in low operating efficiency and poor indoor thermal comfort. It has been shown that varying the speeds of both compressor and outdoor air fan in a variable speed (VS) ASHP unit can lead to different outdoor coil surface temperatures and thus different frosting suppression performances. However, this can also result in different output heating capacities from the ASHP unit. To establish the comprehensive relationship between frosting suppression performances and the total output heating capacity for a VS ASHP unit, an experimental study on developing the condensing-frosting performance maps for a VS experimental ASHP unit under different speed combinations of its compressor and outdoor air fan at three Test Conditions, was carried out and the study results are presented in this paper. The obtained performance maps clearly demonstrated that for the experimental ASHP unit, varying the speeds of its compressor and outdoor air fan would result in not only different outdoor coil surface temperatures, but also different total output heating capacities. A higher outdoor coil surface temperature and thus a better frosting suppression performance may be achieved, but usually at the expenses of losing some of its total output heating capacity. On the other hand, the experimental results also suggested that when the experimental ASHP unit was operated at different speed combinations that can lead to the same or similar total output heating capacities, its operating characteristics in terms of outdoor coil surface states and the total output heating capacity can be remarkably different. The obtained condensing-frosting performance maps may be used as the guidance for the design, operation and control of ASHPs for frost-free operation.
AB - For a space heating ASHP unit, frosting on its outdoor coil would adversely impact its normal operation, requiring frequent defrosting and resulting in low operating efficiency and poor indoor thermal comfort. It has been shown that varying the speeds of both compressor and outdoor air fan in a variable speed (VS) ASHP unit can lead to different outdoor coil surface temperatures and thus different frosting suppression performances. However, this can also result in different output heating capacities from the ASHP unit. To establish the comprehensive relationship between frosting suppression performances and the total output heating capacity for a VS ASHP unit, an experimental study on developing the condensing-frosting performance maps for a VS experimental ASHP unit under different speed combinations of its compressor and outdoor air fan at three Test Conditions, was carried out and the study results are presented in this paper. The obtained performance maps clearly demonstrated that for the experimental ASHP unit, varying the speeds of its compressor and outdoor air fan would result in not only different outdoor coil surface temperatures, but also different total output heating capacities. A higher outdoor coil surface temperature and thus a better frosting suppression performance may be achieved, but usually at the expenses of losing some of its total output heating capacity. On the other hand, the experimental results also suggested that when the experimental ASHP unit was operated at different speed combinations that can lead to the same or similar total output heating capacities, its operating characteristics in terms of outdoor coil surface states and the total output heating capacity can be remarkably different. The obtained condensing-frosting performance maps may be used as the guidance for the design, operation and control of ASHPs for frost-free operation.
KW - Air source heat pump
KW - Condensing-Frosting performance maps
KW - Experimental study
KW - Frosting suppression
KW - Total output heating capacity
KW - Variable speed
UR - http://www.scopus.com/inward/record.url?scp=85127477781&partnerID=8YFLogxK
U2 - 10.1016/j.applthermaleng.2022.118397
DO - 10.1016/j.applthermaleng.2022.118397
M3 - Article
AN - SCOPUS:85127477781
SN - 1359-4311
VL - 211
JO - Applied Thermal Engineering
JF - Applied Thermal Engineering
M1 - 118397